Key takeaways
- Put the specification in the purchase order, not just the product name.
- Every load should arrive with a certificate of analysis, GST invoice and transport documents.
- Know whether you are buying by volume (KL) or weight (MT), and convert using density.
- Check seals, take and keep a sample, and check for water before you unload.
1. Define exactly what you need
- Fuel and grade (for example furnace oil to IS 1593, or LDO)
- Monthly volume and how it is spread across the month
- Delivery point, unloading arrangement and the size of your storage tank
- Any limits your plant must meet, such as sulphur content for stack emissions
2. Put the specification in the purchase order
"Furnace oil, 20 KL" invites argument later. List the properties that matter to your burner and plant, and the acceptable range for each:
| Property | Why it matters |
|---|---|
| Viscosity | Decides heating temperature and how well the fuel atomises |
| Flash point | Safe storage and handling |
| Density | Converts volume to weight; also a quick quality check |
| Sulphur | Stack SOx emissions and corrosion |
| Water and sediment | Flame stability, nozzle blockage, corrosion |
| Ash | Deposits on heat-transfer surfaces |
| Pour point | Whether the fuel flows in cold weather without heating |
| Gross calorific value | Heat you actually get per kilogram |
3. Documents with every load
- Certificate of analysis for that batch
- GST tax invoice
- E-way bill and delivery challan
- Weighbridge slip if you are buying by weight
- Tanker seal numbers recorded on the documents
4. KL or MT? Convert with density
Fuel is sold either by volume in kilolitres (KL) or by weight in metric tonnes (MT). To compare quotes, convert using the density from the certificate:
MT = KL × density (g/cc at 15°C)
For example, 20 KL of LDO at a density of 0.86 is 20 × 0.86 = 17.2 MT. Fuel expands as it warms, so measured volumes are corrected to 15°C. Agree in the contract which basis, and which temperature, the invoice uses.
5. Checks when the tanker arrives
- Check the seals match the numbers on the documents.
- Take a sample from the top, middle and bottom of the tanker. Seal it, label it and keep it until the load is used.
- Check for water with water-finding paste on the dip rod.
- Measure the quantity by weighbridge, flow meter or tank dip, and note the temperature.
- Compare the density of the sample with the certificate. A big gap is a reason to ask questions before unloading.
6. Look after it once it is in your tank
- Drain water from tank bottoms regularly.
- Clean tanks periodically to remove sludge.
- Keep furnace oil at a steady storage and burner temperature.
- Keep strainers and filters clean.
7. Choosing a supplier
- Manufacturer or trader? A manufacturer controls batch quality and availability; a trader depends on someone else's allocation.
- Storage capacity decides whether they can deliver from stock when you need it.
- Track record and references from plants like yours.
- Documentation discipline: certificate, GST invoice and e-way bill on every load, without being asked.
- Response time when something goes wrong.
Kutch Energies manufactures LDO and furnace oil at a 12,000 TPA plant in Anjar, holds 3,000 MT in storage, and ships every load with a quality certificate and GST invoice. We are happy to be measured against this checklist.